Direct Access To Link Devices - Mitsubishi Electric MELSEC iQ-R Series User Manual

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Direct access to link devices

The corresponding data is directly read or written from/to link devices of the RJ71GN11-T2 using the program.
Specify a link device as the link direct device (J\) for direct access.
The link special relay (SB) and link special register (SW) can be set using module label. ( Page 238 _D)
Specification method
Specify the network number and the link devices of the RJ71GN11-T2 for reading or writing data.
(1)
Network number: 1 to 239
\
J
(2)
Remote input (RX): X0 to X3FFF
Remote output (RY): Y0 to Y3FFF
(1) (2)
Remote register (RWw): W0 to W1FFF
Remote register (RWr): W2000 to W3FFF
Link relay (LB): B0 to B7FFF
Link register (LW): W4000 to W7FFF
Link special relay (SB): SB0 to SBFFF
Link special register (SW): SW0 to SWFFF
Ex.
J1\Y0
J1\X0
MOV K20 J1\W0
= J1\W2100 K300
J1\B0
J1\B100
MOV K20 J1\W4200
= J1\W4300 K300
RCPU
No.0
X
RX
RX0
Y
RY
RY0
W
RWr
RWr100
RWw
RWw0
B
LB
LB0
LB
LB100
W
LW
LW200
LW
LW300
No.2
RX
RY
RWr
RWw
LB
LB
LW
LW
1 FUNCTIONS
1.1 Cyclic Transmission
1
31