Input 2 Calibration Procedure - Honeywell UDC2300 Product Manual

Universal digital controller
Hide thumbs Also See for UDC2300:
Table of Contents

Advertisement

Input Calibration
0 to 2 Volts, 0 to 5 Volts, or 1 to 5 Volt Inputs
• Use the copper leads and connect the calibrator to the rear terminals of Input #2
(see Figure 8-8).
• Make sure the jumper of S201 is set for Volts (position 2).
See Figure 2-2 Jumper Placements.
Figure 8-8 Wiring Connections for 1 to 5 Volt Input – Input 2

8.7 Input 2 Calibration Procedure

Preliminary Steps
• Apply power and allow the controller to warm up for 30 minutes before you calibrate.
• Please read Subsection 8.6 – Input 2 Set Up Wiring before beginning the procedure.
• Make sure you have LOCK set to NONE. See Subsection 4.5 - Tuning Set Up
Group.
92
15
+
_
16
Copper
Leads
UDC2300 Controller Product Manual
0 – 2 Volts
0 – 5 Volts
+
1 to 5 Volt
_
Source
24879
Continued next page