Input Calibration
Calibration Steps
Use the following steps when calibrating an input.
Step
1
Find the minimum and maximum range values for your PV input range from Table 8-1.
2
Disconnect the field wiring and find out what equipment you will need to calibrate.
Wire the calibrating device to your controller according to the set up wiring instructions
3
for your particular input (Subsection 8.4 or 8.6).
Follow the calibration procedure given for Input #1 or Input #2 (Subsection 8.5 or 8.7).
4

8.2 Minimum and Maximum Range Values

Select the Range Values
You should calibrate the controller for the minimum (0 %) and maximum (100 %) range
values of your particular controller. If you have a two input controller, calibrate each
input separately.
Select the Voltage or Resistance equivalent for 0 % and 100 % range values from Table
8-1. Use these values when calibrating your controller.
Table 8-1 Voltage and Resistance Equivalents for Input 1 Range Values
Sensor Type
Thermocouples
B
E
E (low)
J
J (low)
K
K (low)
NiNiMoly (NNM68)
NiNiMoly (low)
NiMo-NiCo (NM90)
NiMo-NiCo (low)
Nicrosil Nisil (Nic)
R
S
84
PV Input Range
°F
0 to 3300
–18 to 1816
-454 to 1832
–270 to1000
-200 to 1100
–129 to593
0 to 1600
–18 to871
20 to 770
0 to 2400
–18 to1816
–20 to 1000
–29 to538
32 to 2500
32 to 1260
32 to 2500
32 to 1260
0 to 2372
–18 to1300
0 to 3100
–18 to1704
0 to 3100
–18 to1704
UDC2300 Controller Product Manual
Action
°C
–0.100 mV
–9.835 mV
–6.472 mV
–0.886 mV
–7 to410
–0.334 mV
–0.692 mV
–1.114 mV
0 to1371
0.000 mV
0 to682
0.000 mV
0 to1371
0.000 mV
0 to682
0.000 mV
–0.461 mV
–0.090 mV
–0.092 mV
Range Values
0 %
100 %
13.769 mV
76.373 mV
44.455 mV
50.060 mV
22.400 mV
52.952 mV
22.255 mV
71.330 mV
31.820 mV
71.773 mV
31.825 mV
47.513 mV
20.281 mV
17.998 mV
12/00