6.4 Control Modes

ATTENTION
After changing a Local Setpoint value, if no other key is pressed, it then takes a minimum of thirty (30)
seconds elapsed time before the new value is stored in non-volatile memory. If controller power is
removed before this time, the new setpoint value is lost and the previous setpoint value is used at
power-up. If, after changing the LSP value, another key is pressed, then the value is stored immediately.
6.4.1 Mode Definitions
Control Mode
In automatic local mode, the controller operates from the local setpoints and
AUTOMATIC with
automatically adjusts the output to maintain the PV at the desired value.
LOCAL
In this mode you can adjust the setpoint.
SETPOINT
See Subsection 6.5 - Setpoints.
AUTOMATIC with
In automatic remote mode, the controller operates from the setpoint measured at the
remote setpoint input. Adjustments are available to ratio this input and add a
REMOTE
constant bias before it is applied to the control equation.
SETPOINT
See Subsection 4.9 or 4.10, Input 1 or Input 2.
MANUAL
In the manual mode, the operator directly controls the controller output level. The
process variable and the percent output are displayed. The configured High and Low
Output Limits are disregarded and the operator can change the output value, using
the increment and decrement keys, to the limits allowed by the output type (0 % to
100 % for a time proportioning output or –5 % to 105 % for a current output).
Manual not available with Single Display model.
12/00
Table 6-3 Control Mode Definitions
UDC2300 Controller Product Manual
Definition
Operation
57