Start Up Troublehooting
Symptom
Possible cause
Improper voltage applied
Power connections connec-
ted wrong
Power ground fault
Phase to phase short
Open power
fuses or circuit
breaker trip
Motor overload
Drive overload
Loose connections
Table 8.4
60
Test
See pre-startup check list and
correct if wrong.
Motor and line voltage swap-
ped. Make sure the line in and
motor out are on the correct
terminals. See pre-startup
check list.
Check motor and panel power
wires to ground.
Motor or panel has a short
phase to phase. Check motor
and panel phase to phase for
shorts.
Motor is overloaded for the
application.
Drive is overloaded for the ap-
plication.
Perform pre-startup check for
loose connections.
TR200 Option Panel Operating Instructions
Solution
Correct voltage mismatch.
This could potentially dam-
age panel caution on apply-
ing power recommended.
Correct any wrong connec-
tions. This could potentially
case damage to panel.
Eliminate any ground faults
detected.
Eliminate any shorts detec-
ted.
Perform startup and verify
motor current is within spec-
ifications. If motor current is
exceeding nameplate FLA re-
duce the load on the motor.
Perform startup and verify
drive current is within speci-
fications. If not reduce the
load on the motor.
Tighten loose connections.