Shipping Weights

NOTE WEIGHTS LISTED BELOW ARE APPROXIMATE FOR BASE UNITS. OPTIONS CAN ADD OR REDUCE
WEIGHT OF UNIT. WEIGHTS LISTED ARE IN LBS.
Frame
Tier 1
A2-A3
30
A5
35
B1
65
B2
70
C1
100
C2
130
D1
220
D2
320
Table 3.3
Illustration 3.2: Proper Lifting Method
Cooling
Mount the drive and panel vertically.
Option panels rely on the ambient air for cooling, it is important to observe the limitations on ambient
air temperature. See the following table for temperature rating data. Derating concerns start above
3300 feet elevation above sea level.
Most option panels with drives may be mounted side-by-side without additional side clearance. A2 and
A3 units require 1.5 in. clearance between units (see the next figure).
Top and bottom clearance is required for cooling (see figure
(4 to 10 inches) minimum clearance is required, depending upon the hp (kW) of the unit. See the
mechanical drawing shipped with the unit for specific requirements.
No additional back plate is required for drives with the option panel.
Units may be mounted flush to the wall or free standing. A free-standing mounting kit is available from
Trane.
See table below for temperature ratings.
TR200 Option Panel Operating Instructions
Tier 2
Tier 3
35
55
55
80
85
110
105
180
145
215
190
285
420
585
575
950
28in. min
Cooling Airflow
). Generally, 100 to 250 mm
Installation
15