Start Up
a. Put unit into bypass mode.
b. Check full load amps on terminals T1, T2, and T3. Verify motor amps are within motor FLA rated current and
balanced within 3%. If incorrect, see Troubleshooting Section in this manual for isolation procedures.
For steps 12-14, see sections 5 and 6 in this manual for details.
11. Check operation of any optional functions to confirm they work, as applicable. Options may include run
permissive, fire mode, common start/stop, or others.
12. Exercise safety circuit and verify that unit stops running.
13. Exercise start/stop circuit and verify that unit starts and stops with system in auto mode of operation.