Space - HP FlexFabric 11908-V Installation Manual

Flexfabric 11900 series
Table of Contents

Advertisement

Leave at least 10 cm (3.94 in) of clearance at the inlet and outlet air vents.
The rack for the switch has a good cooling system.
The installation site has a good cooling system.
Verify that the airflow design of the chassis meets the airflow design of the installation site.
Figure 1 Airflow through the 11908-V Chassis
2
(1) Power supply air intake vents
(3) Chassis air intake vents

Space

For easy maintenance, follow these guidelines:
Reserve at least 1 m (3.28 ft) of clearance between the rack and walls or other devices.
The equipment room is at least 3 m (9.84 ft) high.
Rack dimensions are sufficient for the chassis. For more information about chassis specifications,
see
"Appendix A Chassis views and technical
4
5
3
1
(2) Power supply air exhaust vents
(4) Chassis air exhaust vents
specifications."