Can be changed
The "-" sign indicates that the parameter can be changed in any object state and that the
change will be effective immediately.
The information "C(x), T, U" ((x): optional) means that the parameter can be changed only in
the specified drive unit state and that the change will not take effect until the unit switches to
another state. One or more states are possible.
The following states are available:
• C(x) Commissioning
• U
• T
Normalization
Specification of the reference variable with which a signal value is automatically converted for
a BICO interconnection.
The following reference variables are available:
• p2000 ... p2007: Reference speed, reference voltage, etc.
• PERCENT: 1.0 = 100 %
• 4000H: 4000 hex = 100 % (wort) or 4000 0000 hex = 100 % (double word)
• p0514: specific normalization
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Drive commissioning is in progress (p0010 > 0).
Pulses cannot be enabled.
The parameter can only be changed in the following drive commissioning settings
(p0010 > 0):
• C: Can be changed for all settings p0010 > 0.
• C(x): Can only be changed for the settings p0010 = x.
A modified parameter value does not take effect until drive commissioning mode is
exited with p0010 = 0.
Operation
Pulses are enabled.
Ready
The pulses are not enabled and the status "C(x)" is not active.
Refer to the description for p0514[0...9] and p0515[0...19] to p0524[0...19]
2.1 Overview of parameters
C: Commissioning
U: Run
T: Ready to run
2 Parameters
17