Siemens SINAMICS G120 List Manual page 143

Cu250s-2 control units
Hide thumbs Also See for SINAMICS G120:

Advertisement

p0739
BI: CU signal source for terminal DI/DO 25 / CU S_src DI/DO 25
Access level: 1
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for terminal DI/DO 25.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.25 = 1).
DI/DO: Bidirectional Digital Input/Output
p0740
BI: CU signal source for terminal DI/DO 26 / CU S_src DI/DO 26
Access level: 1
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for terminal DI/DO 26.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.26 = 1).
DI/DO: Bidirectional Digital Input/Output
p0741
BI: CU signal source for terminal DI/DO 27 / CU S_src DI/DO 27
Access level: 1
Can be changed: U, T
Unit group: -
Min
-
Description:
Sets the signal source for terminal DI/DO 27.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.27 = 1).
DI/DO: Bidirectional Digital Input/Output
r0747
CU digital outputs status / CU DO status
Access level: 1
Can be changed: -
Unit group: -
Min
-
Description:
Displays the status of digital outputs.
Bit field:
Bit
00
01
02
24
25
26
27
Notice:
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
Inversion using p0748 has been taken into account.
DI/DO: Bidirectional Digital Input/Output
SINAMICS G120 CU250S-2 Control Units
List Manual, 09/2017, A5E33842890
Signal name
DO 0 (NO: T. 19 / NC: T. 18)
DO 1 (NO: T. 21)
DO 2 (NO: T. 24 / NC: T. 23)
DI/DO 24 (T. 51)
DI/DO 25 (T. 52)
DI/DO 26 (T. 53)
DI/DO 27 (T. 54)
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
High
High
High
High
High
High
High
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 2230
Factory setting
0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 2231
Factory setting
0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 2201, 2231
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2130, 2131, 2132,
2133
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
Low
FP
-
-
-
-
-
-
-
143