Carrier Infinity 480CEN024 Installation Instruction page 18

Single-packaged gas furnance, system with 48ce/48cen series puron r-410a refr., single and tree-phase units sizes 024-060
Table of Contents

Advertisement

1.The rated gas i nputs shown inTable 4are foraltitudes
from
sea l evel to2000 f t above sea l evel. These inputs are based
onnatural gas w ithaheating value o f1050 B tu/ft3 a t0.65
specific gravity, orpropane
gas w ith aheating value o f2500
Btu/ft3 a t1.5 specific gravity.
2.For e levations
above 2000 f t,reduce input 4percent foreach
1000 f tabove sea l evel. For e xample
at2001 f t.a12% total
derate isrequired.
3.When the gas s upply being u sed has a different heating value
orspecific gravity, refer t onational and local c odes, or
contact your d istributor todetermine
the required orifice
size.
Ifthe desired gas i nput is115,000 Btuh, only a minor change inthe
manifold pressure
isrequired.
Observe
manifold pressure
and proceed as follows toadjust gas
input:
1.Remove
cover screw o ver regulator
adjustment
screw o n gas
valve.
2.Turn regulator adjustment
screw c lockwise
toincrease
gas
input, orturn regulator
adjustment
screw c ounterclockwise
todecrease
input. Manifold pressure
must bebetween 3.4
and 3.6 in.wg. U nsafe operation
ofthe unit m ay result if
manifold pressure
isoutside this range. Personal
injury o r
unit d amage
may r esult.
UNIT DAMAGE H AZARD
Failure t o follow thiscaution mayresult in component
damage due to flame impingement
of burners andheat
exchangers.
Do Not redrillan orifice. I mproper drilling(burrs,
out-of-round holes, etc.) can cause excessive
burner noise
and misdirection
ofburner flame. If orifice hole appears
damaged
oritissuspected
tohave been redrilled, check orifice
hole w ith anumbered
drill b itofcorrect size.
ADJUST GAS INPUT
The gas i nput tothe unit i sdetermined
bymeasuring
the gas f low
atthe meter orbymeasuring
the manifold pressure.
Measuring
the
gas f lowatthe meter isrecommended
fornatural gas u nits. The
manifold pressure
must bemeasured
todeternaine
theinput o f
propane
gas u nits.
Measure
Gas Flow (Natural Gas Units)
Minor
adjustment
to the gas flow can be made by changing
the
manifold
pressure.
The manifold
pressure
must
be maintained
between
3.4 and 3.6 in. wg.
If larger
adjustments
are required,
change
main burner
orifices
following
the recommendations
of national
and local codes.
NOTE:
All other appliances
that use the same meter must be turned
off when gas flow is measured
at the meter.
Proceed
as follows:
1. Turn off gas supply to unit.
2. Remove
pipe plug on manifold
(See Fig. 16) and connect
manometer.
Turn on gas supply to unit.
3. Record number
of seconds for gas meter test dial to make one
revolution.
4. Divide number
of seconds
in Step 3 into 3600 (number
of
seconds
in one hour).
5. Multiply
result
of Step 4 by the number
of cuft shown for
one revolution
of test dial to obtain cu ft of gas flow per hour.
6. Multiply
result of Step 5 by Btu heating
value
of gas to
obtain total measured
input in Btuh. Compare this value with
heating
input
shown
in Table
4 (Consult
the
local
gas
supplier
if the heating
value of gas is not known).
EXAMPLE:
Assume
that the
size of test dial
is 1 cu ft, one
revolution
takes 32 sec., and the heating
value of the gas is 1050
Btu/ft3.
Proceed
as follows:
1. 32 sec. to complete
one revolution.
2. 3600 + 32 = 112.5.
3. 112.5 x 1 =112.5 ft3 of gas flow/hr.
4. 112.5 x 1050 = 118.125
Btuh input.
FIRE
AND
UNIT DAMAGE
HAZARD
Failure to follow this warning
could result in personal
injury
or death and/or property
damage.
Unsafe operation
of the unit may result if manifold
pressure
is
outside
this range.
3. Replace
cover screw cap on gas valve.
4. Turn
off gas
supply
to unit.
Remove
manometer
from
pressure
tap and replace pipe plug on gas valve. Turn on gas
to unit and check for leaks.
Measure
Manifold
Pressure
(Propane
Units)
The main burner orifices on a propane
gas unit are sized for the unit
rated input when the manifold
pressure
reading
matches
the level
specified
in Table 4.
Proceed
as follows
to adjust gas input on a propane
gas unit:
1. Turn off gas to unit.
2. Remove
pipe plug on manifold
and connect manometer
(See
Fig. 16).
3. Turn on gas to unit.
4. Remove
cover screw over regulator
adjustment
screw on gas
valve.
5. Adjust
regulator
adjustment
screw to the correct
manifold
pressure,
as specified
in Table
4. Turn
adjusting
screw
clock,vise
to increase
manifold
pressure,
or turn adjusting
screw counterclockwise
to decrease
manifold
pressure.
6. Replace
cover screw.
7. Turn off gas to unit. Remove
manometer
from pressure
tap.
Replace
pipe plug on gas valve,
then turn on gas to unit.
Check for leaks.
CHECK
BURNER
FLAME
With
burner
access
panel
removed,
observe
the
unit
heating
operation.
Watch the burner flames to see if they are light blue and
soft in appearance,
and that the flames are approximately
the same
for each burner.
Propane
will have blue flame (See Fig. 17). Refer
to the Maintenance
section for information
on burner removal.
AIRFLOW
AND TEMPERATURE
RISE
The heating
section for each size unit is designed
and approved
for
heating
operation
within the temperature-rise
range stamped
on the
unit rating plate.
Table 5 shows the approved
temperature
rise range for each heating
input,
and the air delivery
cfm at various
temperature
rises. The
heating
operation
airflow must produce
a temperature
rise that falls
within
the approved
range.
Refer to Indoor Airflow
and Airflow
Adjustments
section to adjust
heating
airflow when required.
18

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents