Carrier Infinity 480CEN024 Installation Instruction page 13

Single-packaged gas furnance, system with 48ce/48cen series puron r-410a refr., single and tree-phase units sizes 024-060
Table of Contents

Advertisement

UNIT COMPONENT
DAMAGE H AZARD
Failure tofollow this caution could r esult indamage
tothe u nit
being i nstalled.
1.Make a llelectrical
connections
inaccordance
with NEC
ANSI/NFPA
(latest edition) and local e lectrical codes
governing s uchwiring.In Canada, all electrical
connections
must bein accordance
withCSA standard
C22.1 Canadian
Electrical
(;ode P art 1and a pplicable
local
codes. Refer tounit w iring diagram.
2.Useonlycopper conductor forconnections
between
field-supplied
electrical disconnect
switch a nd unit. D O
NOT USE ALUMINUM WIRE.
3.Be sure t hat high-voltage
power tounit i swithin o perating
voltage range indicated onunit r ating p late. On 3-phase
units, ensure
phases
are balanced
within 2 percent.
Consult
local power company
forcorrection
ofimproper voltage
and/or phase imbalance.
4.Insulate low-voltage
wires f orhighest voltage contained
within c onduit when l ow-voltage
control wires a re i nsame
conduit as high-voltage
wires.
5.Donot d amage
internal components
when d rilling t hrough
any panel tomount electrical
hardware,
conduit, etc.
See u nit wiring l abel 16 or17 and F ig. 1 2 for r eference
when m aking
high voltage and User Interface
control connections.
TRANSFORMER
PROTECTION
The t ransformer
isofthe energy-limiting
type. Itisset t owithstand
a30-sec. overload
orshorted secondary
condition.
HIGH-VOLTAGE
CONNECTIONS
When routing power leads into unit, use only copper wire between
disconnect
and unit. The high voltage leads should be inaconduit
until they e nter the duct panel; conduit termination
at t he duct panel
must bewatertight.
Theunit musthavea separate electrical service w ith a
field-supplied,
waterproof
disconnect
switch mounted
at. o rwithin
sight from, the unit. R efer tothe unit r ating p late. NEC and local
codes formaximum
fuse/circuit
breaker size a nd minimum circuit
amps (ampacity)
forwire sizing ( See Table 3forelectrical
data).
The field-supplied
disconnect
switch box may b emounted
onthe
unit o ver the high-voltage
inlet h ole w hen t he standard
power and
low-voltage
entry p oints a re used ( See Fig. 5 and 6foracceptable
location).
Proceed
as follows tocomplete
the high voltage cnnnections
tothe
unit.
User Interface
._.-
Outdoor
Air Thermistor
HUMIDIFIER
(24 VAC)
LEGEND
Factory Wiring
Field Wiring
......
Infinity
Control
Board
OAT
HUM
W2
Y1
HUM
G
?,OM
r/W1
'/Y2
R
Fig. 12 - Control-Voltage
Connections
A06038
Single phase units:
1. Run the high-voltage
(L1, L2) and ground
lead into the
control box.
2. Connect
ground
lead to chassis ground
connection.
3. Locate the black and yellow wires connected
to the line side
of the contactor.
4. Connect
field L1 to black
wire on connection
11 of the
compressor
contactor.
5. Connect
field wire L2 to yellow wire on connection
23 of the
compressor
contactor.
Three-phase
units:
1. Run the high-voltage
(L1, L2, L3) and ground
lead into the
control box.
2. Connect
ground
lead to chassis ground
connection.
3. Locate the black and yellow wires connected
to the line side
of the contactor.
4. Connect
field L1 to black
wire on connection
11 of the
compressor
contactor.
5. Connect
field wire L2 to yellow wire on connection
13 ofthe
compressor
contactor.
6. Connect
field wire L3 to blue wire from compressor.
13