Carrier Infinity 480CEN024 Installation Instruction page 11

Single-packaged gas furnance, system with 48ce/48cen series puron r-410a refr., single and tree-phase units sizes 024-060
Table of Contents

Advertisement

Table 2 --Maximum
G as Flow Capacity*
NOMINAL
INTERNAL
iRON PiPE
DIAMETER
LENGTH OF PiPE (FT)t
SIZE (iN.)
(iN.)
10
20
30
40
50
60
70
80
90
100
125
150
175
200
1/2
.622
175
120
97
82
73
66
61
57
53
50
44
40
3/4
.824
360
250
200
170
151
138
125
118
110
103
93
84
77
72
1
1.049
680
465
375
320
285
260
240
220
205
195
175
160
145
135
1-1/4
1.380
1400
950
770
600
580
530
490
460
430
400
360
325
300
280
1-1/2
1.610
2100
1460
1180
990
900
810
750
690
650
620
550
500
460
430
Capacity
of pipe
in eu fl of gas per hr for gas pressure
of 0.5 psig or less.
Pressure
drop
of 0.5
in. wg (based
oll a 0.60 specific
gravity
gas).
Refer
to Table.
National
Fire Protec
tion Association
NFPA
54.
This
length
includes
an ordinary
number
of fittings.
Step 8--Install
Gas Piping
The gas
supply
pipe
enters
the
unit
through
the
access
hole
provided.
The gas connection
to the unit is made to the 1/2-in.
FPT
gas inlet on the gas valve.
Install
a gas supply line that runs to the heating
section.
Refer to
Table 2 and the NFGC for gas pipe sizing. Do not use cast-iron
pipe.
It is recommended
that a black iron pipe is used. Check the local
utility
for recommendations
concerning
existing
lines. Size gas
supply
piping for 0.5 in. wg maximum
pressure
drop.
Never use
pipe smaller
than the 1/2-in.
FPT gas inlet on the unit gas valve.
For natural gas applications,
the gas pressure
at unit gas connection
nmst not be less than 4.0 in. wg or greater
than 13 in. wg while the
unit is operating.
For propane
applications,
the gas pressure
nmst
not be less than 7.0 in. wg or greater
than 13 in. wg at the unit
connection.
A
1/8-in.
NPT
plugged
tapping,
accessible
for
test
gauge
connection,
must
be installed
immediately
upstream
of the gas
supply connection
to the gas valve.
When installing
the gas supply line, observe local codes pertaining
to gas pipe installations.
Refer to the NFGC ANSI
Z223.1-2005
NFPA latest edition
(in Canada, CAN/CGA
B 149.1). In the absence
of local
building
codes,
adhere
to
the
following
pertinent
recommendations:
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.
for every 15 ft of length to prevent traps. Grade all horizontal
runs downward
to risers.
Use risers to connect
to heating
section and to meter.
2. Protect all segments
of piping system
against
physical
and
thermal
damage.
Support
all piping with appropriate
straps,
hangers,
etc. Use a minimum
of one hanger
eve_
6 ft. For
pipe sizes
larger than 1/2 in., follow
recommendations
of
national
codes.
3. Apply
joint compound
(pipe dope)
sparingly
and only to
male threads
of joint when
making
pipe connections.
Use
only
pipe
dope
that
is resistant
to action
of liquefied
petroleum
gases as specified
by local and/or national
codes.
Never use Teflon tape.
4. Install sediment
trap in riser leading
to heating
section (See
Fig.
10). This
drip leg functions
as a trap for dirt and
condensate.
5. Install an accessible,
external,
manual
main shutoff valve in
gas supply pipe within
6 ft of heating
section.
6. Install ground-joint
union close to heating
section between
unit manual
shutoff
and external
manual
main shut-off
valve.
7. Pressure
test all gas piping
in accordance
with local
and
national
plumbing
and gas codes before connecting
piping
to unit.
IN
TEE
Fig. 10 - Sediment
Trap
C99020
NOTE:
Pressure
test the gas supply
system
after the gas supply
piping
is connected
to the gas valve. The supply
piping
must be
disconnected
from the gas valve
during
the testing
of the piping
systems when test pressure
is in excess of 0.5 psig. Pressure
test the
gas supply piping system at pressures
equal to or less than 0.5 psig.
The unit heating
section must be isolated from the gas piping system
by closing
the external
main manual
shutoff
valve
and slightly
opening
the ground-joint
union.
FIRE OR EXPLOSION
HAZARD
Failure
to follow this warning
could
result in fire, explosion,
personal
injury, death and/or property
damage.
-Connect
gas pipe to unit using
a backup
wrench
to avoid
damaging
gas controls.
-Never
purge a gas line into a combustion
chamber.
Never test
for gas leaks with an open flame. Use a commercially
available
soap solution
made specifically
for the detection
of leaks to
check all connections.
-Use
proper
length
of pipe to avoid
stress
on gas control
manifold.
-If a flexible
connector
is required
or allowed
by authority
having jurisdiction,
black iron pipe shall be installed
at furnace
gas valve and extend a minimunr
of 2 in. outside furnace casing.
-If
codes
allow
a flexible
connector,
always
use
a new
connector,
do not
use a connector
which
has
previously
serviced
another
gas appliance.
n
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents