Technical Data, 690 V Inverters; General Data, 690 V Inverters - Siemens SINAMICS G12 Hardware Installation Manual

Pm240-2 power modules, ip20 / push-through technology (pt)
Table of Contents

Advertisement

7.7

Technical data, 690 V inverters

Motors for 690 V Power Modules
For the 690 V Power Modules, induction motors are permissible in the range from 50
% ... 150 % of the inverter power without any restrictions.
Note
Motors for inverter operation
Only use motors that are suitable for operation with inverters with a DC link.
For 690 V Power Modules, motors with a suitable insulation system for 690 V inverter operation
are required (e.g. PREMIUM).
7.7.1

General data, 690 V inverters

Property
Line voltage
Line supply configurations
Line impedance
Power factor λ
Output voltage
Input frequency
Output frequency
Inrush current
Overvoltage category ac‐
cording to EN 61800-5-1
Pulse frequency
Short-circuit current rating
(SCCR) and branch protec‐
tion
Braking methods
Degree of protection ac‐
cording to EN 60529
Protection class according
to EN 61800-5-1
Touch protection accord‐
ing to EN 50274
Cooling in compliance with
EN 60146
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
Version
● for systems according to IEC: 3-ph. AC 500 V ... 690 V ± 10% (in operation -20% < 1 min)
● for systems according to UL
filtered devices only with Slash Rating (600Y/347V AC)
Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 50)
No restrictions
> 0.9
3-ph. AC 0 V ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
< LO base load input current
III for line supplies
2 kHz (factory setting), can be adjusted to 4 kHz
If you increase the pulse frequency, the inverter reduces the maximum output current.
≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
support.industry.siemens.com/cs/ww/en/view/109479152)
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20; must be installed in a control cabinet
The inverters are devices with protection class I
DGUV regulation 3 when used for the intended purpose
Forced air cooling AF
7.7 Technical data, 690 V inverters
3-ph. AC 500 V ... 600 V ± 10% (in operation -20% < 1 min)
Technical data
(https://
101