Replacement scenario of an IM 155-6 PN HS or of a BusAdapter
In a replacement scenario, any IO device or BusAdapter in operation must be reset to its
delivery state via "Reset to factory settings" (see the system manual ET 200SP distributed
I/O system (http://support.automation.siemens.com/WW/view/en/58649293)).
Media redundancy (MRP)
Function for safeguarding communication and system availability. A ring topology ensures
that an alternative communication path is made available if a transmission route fails.
You can find more information on this topic in the STEP 7 online help and
● As of STEP 7 V14, in the PROFINET with STEP 7 V14
(http://support.automation.siemens.com/WW/view/en/49948856) function manual
● As of STEP 7 V5.5, in the PROFINET System Description
(http://support.automation.siemens.com/WW/view/en/19292127) system manual
Media redundancy with planned duplication (MRPD)
If bumpless media redundancy is to be reached with short update times (together with IRT),
you must use the MRP extension "Media redundancy with planned duplication (MRPD)".
You can find more information on this topic in the STEP 7 online help and
● As of STEP 7 V14, in the PROFINET with STEP 7 V14
(http://support.automation.siemens.com/WW/view/en/49948856) function manual
● As of STEP 7 V5.5, in the PROFINET System Description
(http://support.automation.siemens.com/WW/view/en/19292127) system manual
Shared device
IO device which makes its data available to multiple IO controllers.
The interface module supports shared device at submodule level.
Notes on configuring:
● Always load hardware changes to all affected IO controllers.
● Set the same send clocks in the projects.
● Limit the I/O data including user data qualifier to 360 bytes per IO controller.
● Use the same station name and the same IP address for each shared configuration.
● Assign each module or submodule to only one IO controller.
● In the case of an incorrect configuration, you may need to perform a power OFF/ON on
the interface module.
You can find more information on this topic in the STEP 7 online help and
● As of STEP 7 V14, in the PROFINET with STEP 7 V14
(http://support.automation.siemens.com/WW/view/en/49948856) function manual
● As of STEP 7 V5.5, in the PROFINET System Description
(http://support.automation.siemens.com/WW/view/en/19292127) system manual
IM 155-6 PN HS interface module (6ES7155-6AU00-0DN0)
Manual, 09/2016, A5E34928647-AA
Product overview
2.2 Functions