Product overview
2.1 Properties
First BaseUnit of an ET 200SP in the configuration
The interface modules support dark-colored BaseUnits in slot 1. This means that modules
without a connection to the integrated voltage buses P1 and P2 can be configured starting
with slot 1. Currently, this applies to the following modules:
● AI EnergyMeter
● DI 4x120..230VAC ST (6ES7131-6FD00-0BB1)
● DQ 4x24..230VAC/2A ST (6ES7132-6FD00-0BB1)
● RQ 4x120VDC-230VAC/5A NO ST (6ES7132-6HD00-0BB1)
● RQ 4x120VDC-230VAC/5A NO MA ST (6ES7132-6MD00-0BB1)
Note
First BaseUnit of an ET 200SP in the configuration
The first BaseUnit of an ET 200SP station may be a dark-colored one if an AC I/O module or
AI Energy Meter is plugged. Please observe the information on limiting the overvoltage and
power rating in the AC I/O module manuals.
A light-colored BaseUnit must be plugged into the slot of the first 24 V DC I/O module to
supply the 24 V DC supply voltage.
Pay attention to the type of the BaseUnits during the configuration.
14
IM 155-6 PN HS interface module (6ES7155-6AU00-0DN0)
Manual, 09/2016, A5E34928647-AA