Trane RTWD Installation Operation & Maintenance page 88

Series r helical rotary water-cooled liquid and compressor chillers
Table of Contents

Advertisement

Service and Maintenance
Figure 20 - Waterbox Removal - Remove Bolts
long bolt
long bolt
long bolt
L a b e l
L a b e l
Label
Figure 21 - Waterbox Removal - Slide Out, Install Safety
Hoist Ring
D ring
Figure 22 - Waterbox Removal - Swing Out, Install Lifting
Chain
88
drill point m ark
drill point m ark
drill point mark
WARNING
OVERHEAD HAZARD!
Never stand below or in close proximately to heavy
objects while they are suspended from, or being lifted by,
a lifting device. Failure to follow these instructions could
result in death or serious injuries.
All RTWD Units
1. Store waterbox in a safe and secure location and
position.
Note: Do not leave waterbox suspended from lifting
device.
2. Work a round nylon or brass bristled brush (attached
to a rod) in and out of each of the condenser water
tubes to loosen the sludge.
3. Thoroughly fl ush the condenser water tubes with
clean water.
Note: (To clean internally enhanced tubes, use a
bi-directional brush or consult a qualifi ed service
organization for recommendations.)
Reassembly
Once service is complete, the waterbox should be
reinstalled on the shell following all previous procedures
in reverse.
Use new o-rings or gaskets on all joints after thoroughly
cleaning each joint.
• Torque waterbox bolts.
• Torque bolts in a star pattern. Refer to table below for
torque values.
Note: Torque bolts in a star pattern.
Torque Values
Evaporator
88 Nm
Condenser
(RTWD only)
88 Nm
RLC-SVX14H-GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rtud

Table of Contents