General Electrical Recommendations
CAUTION! To avoid corrosion, overheating or general
damage, at terminal connections, unit is designed for
copper mono-conductors only. In case of multiconductor
cable, an intermediate connection box must be added.
For cable with alternative material, bi-material connecting
devices are mandatory. Cable routing inside control panel
should be made case by case by installer.
Do not allow conduit to interfere with other components,
structural members or equipment. Control voltage
(115V) wiring in conduit must be separate from conduit
carrying low voltage (<30V) wiring. To prevent control
malfunctions, do not run low voltage wiring (<30V) in
conduit with conductors carrying more than 30V.
WARNING!
The Warning Label is displayed on the equipment
and shown on wiring diagrams and schematics. Strict
adherence to these warnings must be observed. Failure
to do so may result in personal injury or death.
CAUTION! Units including RTWD HSE units must not
be linked to the neutral wiring of the installation. Units
are compatible with the following neutral operating
conditions:
TNS
IT
Standard
Special
* Differential protection should be suited for industrial
machinery with current leak which can be higher than
500 mA (several motors and frequency drives).
38
TNC
TT
Special
Standard*
Electrical data tables
The electrical data details is given in the tables
contained in this chapter. the data are function of the
confi guration of the unit and the following digit of the
model number
- Unit effi ciency (Digit 12)
- Unit application (Digit 15)
- Evaporator application (Digit 21)
- Compressor starter type (Digit 24)
The following data are defi ned
- Unit Maximum Power input (kW)
- Unit rated amps (Max compr + Control)
- Unit start up amps (Starting Amps of the largest
compr+RLA of 2nd compr+ control)
-Unit Displacement Power factor
- Disconnect switch size (A)
- Oil Separator Crankcase Heater:
2 x 125 W whatever the size RTWD/RTUD
- Compressor Crankcase Heater:
2 x 150 W whatever the size RTWD/RTUD
- Control Circuit: Factory installed transformer whatever
the size RTWD/RTUD
- Short Circuit Intensity: 35 KA max whatever the size
RTWD/RTUD
For each circuit
- Compressor motor RLA
- Compressor motor LRA
- Compressor motor max Amps
- Compressor motor max Power Input
Note: Rating is made for 400 V, 3 phases, 50 Hz
power supply.
RLC-SVX14H-GB