Trane RTWD Installation Operation & Maintenance page 11

Series r helical rotary water-cooled liquid and compressor chillers
Table of Contents

Advertisement

Table 2 - RTWD High Effi ciency - R134a (Continued)
Indicative performances
Cooling Capacity (1)
Total Power input in cooling (1)
Heating Capacity (2)
Total Power input in heating (2)
Compressor
Compressor Number per Circuit
Type
Model
Evaporator
Quantity
Type
Evaporator model
Evaporator Water Content volume
Two pass evaporator
Evap. Water Flow rate - Minimum (3) (l/s)
Evap. Water Flow rate - Maximum
(3)
Nominal water connection size
(Grooved coupling)
Three pass evaporator
Evap. Water Flow rate - Minimum (3) (l/s)
Evap. Water Flow rate - Maximum
(3)
Nominal water connection size
(Grooved coupling)
Condenser
Quantity
Type
Condenser model
Condenser Water Content volume
Two pass condenser
Cond. Water Flow rate - Minimum
Cond. Water Flow rate - Maximum
Nominal water connection size
(Grooved coupling)
Dimensions (4)
Unit Length
Unit Width
Unit Height
Weights (5)
Shipping Weight
Operating Weight
System data (6)
Nb of refrigerant circuit
Minimum cooling load %
Standard unit
R134a refrigerant charge Circuit1 /
Circuit 2 (6)
Oil charge Circuit1 / Circuit 2
POE Oil type
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser water temperature 30°C/35°C - for detailed performances consult
order write up.
(2) Indicative performance at Evaporator water temperature: 10°C / 7°C - Condenser water temperature 40°C/45°C - for detailed performances consult
order write up.
(3) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(4) These dimensions are the maximum for a specifi c size, they may vary from one confi guration to another within a same size. For accurate
dimensions of a specifi c confi guration, refer to relevant submittal drawings.
(5) All weights +/-5% and are the maximum for each size and may vary from one confi guration to another for the same size (add 62kg for unit with
acoustic package) and refer to relevant drawing for a specifi c confi guration.
(6) System data are indicative and subject to change without notice. Please refer to unit nameplate data.
RLC-SVX14H-GB
RTWD
RTWD
130
140
(kW)
488
531
(kW)
99
107
(kW)
512
562
(kW)
116
128
#
1/1
1/1
M1/M1
M1/M2
#
1
1
E3AM3
E3AM2
(l)
72.6
77.0
8.8
9.5
(l/s)
32.4
34.9
(in) -
DN125-5'
DN125-5'
(mm)
(139.7 mm)
(139.7 mm)
5.9
6.4
(l/s)
21.6
23.3
(in) -
DN150-6"
DN150-6"
(mm)
(168.3 mm)
(168.3 mm)
#
1
1
C3AM3
C3AM2
(l)
81.7
86.8
(l/s)
10
11
(l/s)
37
40
(in) -
DN150-6'
DN150-6'
(mm)
(168.3 mm)
(168.3 mm)
(mm)
3400
3400
(mm)
1280
1280
(mm)
1950
1950
(kg)
3616
3638
(kg)
3771
3802
#
2
2
%
30
30
(kg)
61/61
60/62
(l)
9.9/9.9
9.9/9.9
RTWD
RTWD
RTWD
160
180
579
638
700.1
114
127
138.7
616
677
740.1
139
154
167.9
1/1
1/1
Screw
M2/M2
M2/N1
N1/N1
1
1
Flooded shell and tube heat exchanger
E3AM1
E3AMJ
E5AM2
85.0
91.0
10.7
11.7
13.3
39.1
43.0
48.6
DN125-5'
DN125-5'
DN150-6'
(139.7 mm)
(139.7 mm)
(168.3 mm)
7.13
7.82
8.83
26.12
28.64
32.43
DN150-6"
DN150-6"
DN150-6"
(168.3 mm)
(168.3 mm)
(168.3 mm)
1
1
Shell and Tube Heat Exchanger
C3AM1
C3AMJ
C5AM2
93.0
99.0
12
13
15.4
44
48
56.4
DN150-6'
DN150-6'
DN150-6'
(168.3 mm)
(168.3 mm)
(168.3 mm)
3400
3490
3490
1280
1310
1310
1950
1970
2010
3668
3851
4262
3846
4042
4488
2
2
30
30
61/61
60/62
81/81
10/10
10/12
12/12
OIL048E or OIL023E
General data
RTWD
RTWD
200
220
250
765
836
155
168
812.9
888.4
184.6
199.6
1/1
1/1
1/1
N1/N2
N2/N2
1
1
1
E5AM1
E5AMJ
108
113.3
120.3
14.1
15.1
51.5
55.3
DN150-6'
DN150-6'
(168.3 mm)
(168.3 mm)
9.3
10.1
34.3
36.9
DN150-6"
DN150-6"
(168.3 mm)
(168.3 mm)
1
1
1
C5AM2
C5AM1
118
117.8
133.3
15.4
18
56.4
65.9
DN150-6'
DN150-6'
(168.3 mm)
(168.3 mm)
3490
3490
1310
1310
2010
2010
4273
4326
4594
4579
2
2
2
30
30
30
80/83
82/82
11.7/11.7
11.7/11.7
11