Digital outputs
Number of outputs
Sinking output
Sourcing output
Short-circuit protection
Switching capacity of outputs
With resistive load, max.
With lamp load, max.
Output voltage
For signal "1", min.
Output current
For signal "1" rated value
For signal "1" permitted range, min.
For signal "1" permitted range, max.
For signal "0" residual current, max.
Output delay with resistive load
"0" to "1", max.
"1" to "0", max.
Parallel switching of 2 outputs
For logic operations
For increased performance
For redundant control of a load
Switching frequency
With resistive load, max.
With inductive load, max.
With lamp load, max.
Total current of outputs
Current per channel, max.
Current per module, max.
Total current of outputs (per module)
Horizontal installation
Vertical installation
Output current per channel
Horizontal installation
Vertical installation
DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1)
Manual, 03/2015, A5E32043575-AB
up to 40 °C, max.
up to 50 °C, max.
up to 60 °C, max.
up to 30 °C, max.
up to 40 °C, max.
up to 50 °C, max.
up to 60 °C, max.
up to 50 °C, max.
Technical specifications
6.1 Technical specifications
6ES7132-6FD00-0BB1
4
No
Yes
No; install a fuse with 10A trigger current when
using a type B1 BU
2 A
100 W
20.4 V
2 A
10 mA
2 A
460 µA
10 ms
10 ms
No
No
Yes
10 Hz
0.5 Hz
1 Hz
2 A
8 A
8 A
6 A
4 A
8 A
6 A
4 A
2 A
2 A
19