Connection: 2-wire and 3-wire connection of actuators
The following figure shows the block diagram and an example for the terminal assignment of
the digital input module DQ 4x24..230VAC/2A ST on the BaseUnit BU type B1.
2-wire connection
3-wire connection
Backplane bus interface
Output electronics
Color identification label CCxx (optional)
DQ
Output signal, channel n
n
L1
Encoder supply
P1,
Internal self-assembling voltage buses
P2,
Connection to left (dark-colored BaseUnit)
AUX
Figure 3-1
Wiring and block diagram for 2-wire and 3-wire connection of actuators
No connection for three-phase loads
The digital output is not suitable for three-phase loads.
DQ 4x24..230VAC/2A ST digital output module (6ES7132-6FD00-0BB1)
Manual, 03/2015, A5E32043575-AB
3.1 Wiring and block diagram
N
Neutral
1L, 2L
Supply voltage 120 V AC to 230 V AC
1N, 2N
Neutral conductor supply voltage
PE (AUX)
Protective conductor connection
DIAG
Diagnostics LED (red/green)
.0, .1, .2, .3
Channel status LED (green)
PWR
Power LED (green)
Wiring