Sfp+ Cable; Qsfp+ Cable - HP FlexFabric 12900 series Installation Manual

Hide thumbs Also See for FlexFabric 12900 series:
Table of Contents

Advertisement

Never bend or curve a fiber when connecting it. After a fiber is installed well, the bend radius must
be not less than 40 mm (the minimum dynamic bend radius is 20 D, and the minimum static bend
radius is 10 D. D indicates the outer diameter of dust caps).
If the fiber has to pass through a metallic board hole, the hole must have a sleek and fully filleted
surface (the filleting radius must be not less than 2 mm). When passing through a metallic board
hole or bending along the acute side of mechanical parts, the fiber must wear jackets or cushions.
Insert and remove a plug with care. Never exert a fierce force to the fiber or plug; otherwise the
plug may be damaged or the fiber may be broken. Never pull, press or extrude the fiber fiercely.
For the allowed maximum tensile load and crush load, see

SFP+ cable

You can use SFP+ cables to connect the SFP+ ports. The SFP+ cables available for the switch series are
10 G SFP+ Cu cables, as shown in
Figure 58 SFP+ cable
1
(1) Connector

QSFP+ cable

You can use QSFP+ cables to connect the QSFP+ ports.
Figure 59 QSFP+ cable
(1) Connector
Figure
2
Table
58.
(2) Pull latch
(2) Pull latch
90
54.