Table 23 Analog Output Configuration Parameters - Honeywell HC900 Reference Manual

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Function Blocks
AO Function Block
Configuration parameters
AO's Address starts at Module 4.
Properties Group
Block
Order
Address
Rack
I/O Module
Channel
Range
Range Hi
Range Low
Output
mA at range
High
mA at Low
Range
Output Limits
mA at range
High Limit
mA at Low
Range Limit
Failsafe
Failsafe
Value
Failsafe Type
Slew Time in
Slew Rate
seconds
80

Table 23 Analog output configuration parameters

Parameter
Index #
N/A
1
2
3
4
5
6
7
8
9
HC900 Hybrid Control Designer Function Block Reference Guide
Parameter Description
Execution Order for Block
This is the address of the
selected Rack.
Address of selected I/O
module (must match model
selection guide)
Channel on selected I/O
Module
High Range Value Engineering
Unit - value of input that
corresponds to 100 % output
value
Low Range Value Engineering
Unit - value of input that
corresponds to 0 % output
value
Value of mA output that
corresponds to 100 % output
signal (for example: 20 mA)
Value of mA output that
corresponds to 0 % output
signal (for example: 4 mA)
Value of mA that you want to
set the High Range Limit
Value of mA that you want to
set the Low Range Limit
Failsafe Value
Type of Failsafe
Slew Rate is the maximum rate
of change required to drive the
output from full OFF (0% -
typically 4 mA) to full ON
(100% - typically 20mA). The
Value or Selection
Read Only. To change
block order, right-click on
a Function Block and
select Execution Order.
Enter a value
from 1 to 5.
Enter a value:
from 1 to 12
Enter a value:
from 1 to 4
-99999 to 999999
Default = 100
-99999 to 999999
Default = 0.0
0 to 20
Default = 20
0 to 20
Default = 4
0 to 21
Default = 21
0 to 21
Default = 0
0 to 21 mA
Default = 0
High - sets the output of
the block to High Output
Range limit when failure is
detected
Low - sets the output of
the block to Low Output
Range Limit when failure
is detected
Hold - hold the output at
the last value just prior to
the failure being detected
Enter a value of from 0.0
to 99
Revision 11