Honeywell HC900 Reference Manual page 122

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Function Blocks
CARB Carbon Potential Function Block
Properties Group
Reset
Minutes
or
Repeats/
Minute
Rate
Minutes
Feedforward Gain
Feed-
Forward
Gain
Manual Reset
Manual
Reset
ATTENTION
DUPA and DUPB algorithm types automatically select tuning set #2 for outputs between
50 % and –5 %. Tuning set #2 must be entered for DUPA and DUPB.
108
Parameter
Index #
2
Reset 1
38
Reset 2
1
Rate 1
37
Rate 2
43
32
HC900 Hybrid Control Designer Function Block Reference Guide
Parameter Description
RESET (Integral Time) -
adjusts the controller's output
according to both the size of
the deviation (SP-PV) and the
time it lasts. The amount of
corrective action depends on
the value of Gain.
The reset adjustment is
measured as how many times
proportional action is repeated
per minute (Repeats/minute)
or how many minutes before
one repeat of the proportional
action occurs
(Minutes/repeat).
RATE action, in minutes
affects the controller's output
whenever the deviation is
changing; and affects it more
when the deviation is changing
faster.
Applies Gain to the
Feedforward value (FFV).
Feedforward Input is multiplied
by this value.
MANUAL RESET- is only
applicable if you do not use
RESET (Integral Time).
Value or Selection
0.02 to 50.00
Must be enabled for
PID-B or DUP-B algorithm
selections.
0 or 0.1 to 10.00 minutes
0 = OFF
0.0 to 10.0
–100 to 100
(in % of Output)
Revision 11
2/07