Function Blocks
SPS Setpoint Scheduler Function Block
Inputs
ENABL= Level input to enable the block. Only checked in ready state.
Input is ignored if not connected.
NPGM = Program Number (when SET is ON). See ATTENTION below.
NSEG = Starting Segment Number (when SET is ON). See ATTENTION below.
^SET = Pulse Input to load NPGM and SEG numbers. See ATTENTION below.
st
= 1
Process Variable
PV1
nd
= 2
Process Variable
PV2
rd
= 3
Process Variable
PV3
th
= 4
Process Variable
PV4
th
= 5
Process Variable
PV5
th
= 6
Process Variable
PV6
th
= 7
Process Variable
PV7
th
= 8
Process Variable
PV8
STRQ = for connection to the STQR output of the STSW function block. (See
block encodes discrete inputs to a form that will convey change mode requests from the STSW block:
0.0
1.0
2.0
4.0
8.0
16.0
32.0
ATTENTION
If either or both NPGM and NSEG are connected directly to analog variables, when that
analog variable changes (for example: via a recipe load), then the Setpoint Scheduler block
will immediately use the new value internally.
If NPGM or NSEG is connected to any other function type then their values are loaded into the
SP Scheduler only when ^SET goes through a positive transition.
Outputs
= Current Program Number
PGM
= Current Segment number
SEG
= Program State (Reset, Run, Hold, Ghold, Stop).
STA
= Setpoint #1 Output (EU)
SP1
= Setpoint #2 Output (EU)
SP2
= Setpoint #3 Output (EU)
SP3
= Setpoint #4 Output (EU)
SP4
= Setpoint #5 Output (EU)
SP5
= Setpoint #6 Output (EU)
SP6
= Setpoint #7 Output (EU)
SP7
= Setpoint #8 Output (EU)
SP8
354
No Change
Jog State
Guaranteed Hold State
Reset State
Hold State
Run State
Advance state
HC900 Hybrid Control Designer Function Block Reference Guide
F igure 101.) The STSW
H
Revision 11
2/07