Service Pin Request; Model Wzs Sensor; Model Wds Sensor - Trane WDS Installation, Operation And Maintenance Manual

Wireless sensors
Table of Contents

Advertisement

Service Pin Request

Model WZS and WDS sensors can communicate a service pin request to their associated
receivers.

Model WZS Sensor

To initiate a service pin request, press the Occupied button
seconds. The following occurs:

Model WDS Sensor

To initiate a service pin request, the sensor must be configured to support occupancy and
must be in operating mode (see
p.
To initiate a service pin request:
1. With the sensor in operating mode, navigate to the occupancy menu.
2. Press the right arrow on the keypad
3. Press and hold the center button for 10 seconds. The following occurs:
Figure 6.
BAS-SVX04C-EN • Wireless Sensors
Space temperature output is driven to 10 Ω (nominal).
The output generates for 15 seconds.
22).
screen; the unoccupied symbol leaves the screen.
The wrench symbol
A service pin request is initiated.
Space temperature output is driven to 10 Ω (nominal).
The output generates for 15 seconds.
After 15 seconds, the wrench symbol disappears.
WDS sensor: Location of keys for service pin request
Center button
"Configuring the Wireless Sensor (Model WDS only), "
(Figure
6). The occupied symbol remains on the
appears.
Operation
(Figure 5, p.
28) for 10–25
Right arrow key
29