Siemens SIMATIC ET 200SP Manual page 8

Ha digital output module dq 16x24vdc/0.5a
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Product overview
2.1 Properties of the I/O module DQ 16x24VDC/0.5A HA
Properties
The I/O module has the following technical properties:
● 16 digital outputs with the following properties that can be individually configured for each
channel
– Configurable diagnostics
– Configurable substitute values
● Source output (PNP, switching to P potential)
● Module-specific configurable diagnostics for missing supply voltage L+
● Output current 0.5 A per channel
● Suitable for solenoid valves, DC contactors, and indicator lights
The I/O module supports the following functions:
● Firmware update
● I&M identification data
● Parameter reassignment in RUN
● Value status QI
● IO redundancy
● Output disable switch
You can configure the I/O module with HW Config and integrate it into your system.
Output disable switch
If you want to pull the I/O module in runtime, you have to press the output disable switch for
3 seconds for the I/O module to be deenergized.
When the output disable switch has been pressed for 3 seconds, the LED DIAG flashes red,
the LED MT lights up yellow and the I/O module generates a diagnostics message. See section
Status and error displays of the I/O module DQ 16x24VDC/0.5A HA (Page 17).
Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.
Accessories
The following accessories must be ordered separately:
● Labeling strips
● Color-coded labels
● Reference identification label
● Shield connector
8
Digital output module DQ 16x24VDC/0.5A (6DL1132-6BH00-0PH1)
Manual, 05/2017, A5E39265993-AA

Advertisement

Table of Contents
loading

Table of Contents