Siemens SIMATIC ET 200SP Manual page 24

Ha digital output module dq 16x24vdc/0.5a
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Technical specifications
Article number
Height
Depth
Weights
Weight, approx.
Derating curve
The following figure shows the load current derating with horizontal and vertical mounting
positions.
9.00
8.00
7.00
6.00
5.00
4.00
3.00
2.00
1.00
0.00
-40
Note
You can avoid the derating by deactivating channels 8 to 16.
Test current for signal state "0"
Note
If the "Check for wire break" parameter is activated, a test current flows, even if the signal state
for the output is "0" (singular mode: Approx. 700 μA, redundant operation: approx. 1.4 mA).
Cycle time
The cycle time describes the time slice in which signals from the inputs are acquired and
processed. The cycle time of the I/O module is 1 ms.
24
-20
0
20
6DL1132-6BH00-0PH1
115 mm
138 mm
137 g
40
60
80
Digital output module DQ 16x24VDC/0.5A (6DL1132-6BH00-0PH1)
Total current I / A
Horizontal mounting position
Total current I / A
Horizontal mounting position
Manual, 05/2017, A5E39265993-AA

Advertisement

Table of Contents
loading

Table of Contents