Technical specifications
Article number
Digital outputs
Number of digital outputs
Current-sinking
Current-sourcing
Short-circuit protection
● Response threshold, typ.
● Response threshold, typ.
Open-circuit detection
Overload protection
Limitation of inductive shutdown voltage to
Controlling a digital input
Switching capacity of the outputs
● with resistive load, max.
● on lamp load, max.
Load resistance range
● lower limit
● upper limit
Output current
● for signal "1" rated value
● for signal "0" residual current, max.
Output delay with resistive load
● "0" to "1", typ.
● "1" to "0", typ.
Parallel switching of two outputs
● for uprating
● for redundant control of a load
Switching frequency
● with resistive load, max.
● with inductive load, max.
● on lamp load, max.
Total current of the outputs
● Current per channel, max.
● Current per module, max.
Total current of the outputs (per module)
horizontal installation
22
up to 30 °C, max.
up to 40 °C, max.
6DL1132-6BH00-0PH1
16
No
Yes
Yes; Ensure sufficient low-resistance cable routing
to the sensor/actuator in order to attain the re‐
sponse threshold. Depending on the cable cross-
section used, there may be constraints regarding
the usable length of cable.
0.7 A to 1.3 A (for IO redundancy up to max 2.6 A)
0.7 A to 1.3 A (for IO redundancy up to max 2.6 A)
Yes; 0.7 mA test current for wire-break diagnos‐
tics; this value is doubled in the case of IO redun‐
dancy
Yes
L+ -(37 to 41V)
Yes
0.5 A
5 W
48 Ω
12 kΩ
0.5 A
0.7 mA; Test current for wire-break diagnostics;
this value is doubled in the case of IO redundancy
50 µs
100 µs
No
Yes
100 Hz
2 Hz
10 Hz
0.5 A
8 A
8 A
8 A
Digital output module DQ 16x24VDC/0.5A (6DL1132-6BH00-0PH1)