[3-02] Status: defines whether temperatures above 60°C can be
selected (1) or not (0).
INFORMATION
The
maximum
temperature by heat pump operation is limited to
60°C. A higher temperature set point is only
possible by electric booster heater operation.
When this field setting is not activated, the
booster heater will still work if the ambient
temperature drops below the value set in [7-04].
This is the backup mode of the domestic hot
water heat pump.
[3-03] Status: defines whether the heat up can continue (1) or
not (0) when the requested temperature set point is not reached
during the programmed schedule timer operation. The p icon is
blinking in case the heat up can not continue ([3-03]=0).
In case the reheat function is enabled, the p icon will stop
blinking when the reheat operation has finished.
[4] Miscellaneous
[4-03] Simultanuous operation of booster heater and heatpump
■ [4-03]=0 Simultanuous operation of the electric booster
heater and heat pump is not allowed.
■ [4-03]=1 Simultanuous operation of the booster heater and
heat pump is only allowed during quiet mode. During quiet
operation the heat pump operation sound is reduced by
reducing the compressor frequency.
heating capacity and increases the heat up cycle time.
If required the electric booster heater can assist to heat up
the domestic hot water tank to shorten the heat up cycle
time.
■ [4-03]=2 Simultanuous operation of the booster heater and
heat pump is only allowed during powerful operation mode.
The powerful operation mode is considered as an
exceptional operation mode.
operation the electric booster heater can assist to heat up the
domestic hot water tank.
■ [4-03]=3 Allows the simultanuous operation of electric
booster heater and heat pump during quiet and powerful
operation.
Installation manual
20
domestic
hot
water
tank
This influences the
If required during powerful
[6] Miscellaneous
[6-00] and [6-01]: The 'DT (temperature difference) for heat pump
domestic water heating mode' field settings determine the
temperatures at which heating of the domestic hot water by the heat
pump will be started (i.e., the heat pump ON temperature) and
stopped (i.e., the heat pump OFF temperature).
When the domestic hot water temperature drops below the heat
pump ON temperature (T
HP ON
the heat pump will be started. As soon as the domestic hot water
temperature reaches the heat pump OFF temperature (T
the user set point temperature (T
by the heat pump will be stopped.
The heat pump OFF temperature, and the heat pump ON
temperature, and its relation with field settings [6-00] and [6-01] are
explained in the illustration below.
[6-00] Start: temperature difference determining the heat pump
ON temperature (T
HP ON
[6-01] Stop: temperature difference determining the heat pump
OFF temperature (T
HP OFF
T
<60°C
U
T
= 45°C
U
T(°C)
[6-01] =
0°C
[6-00] =
5°C
60
T
HP MAX
45
T
= T
U
HP OFF
[6-00]
40
T
HP ON
T
User set point temperature (as set on the user interface)
U
T
Maximum domestic hot water tank temperature at sensor in
HP MAX
domestic hot water tank by heat pump operation
T
Heat pump OFF temperature
HP OFF
T
Heat pump ON temperature
HP ON
[6-02] Booster heater economical timer: determines when the
booster heater can start after the heat pump has started
operating. This
setting
simultanuous operation of the booster heater and heat pump is
allowed ([4-03] is not set to 0).
[6-03] Powerful mode priority: determines the priority when quiet
operation mode and powerful operation mode are active at the
same moment.
[6-03]
Powerful
priority
setting
OFF
0
OFF
Normal
ON
Powerful
1
OFF
Normal
ON
Powerful
If [6-03] is set to 1, powerful operation mode has priority over
quiet operation mode.
[6-04] Quiet mode level: defines the level of noise reduction.
There are 3 levels of noise reduction during operation in quiet
mode, where level 3 is the most quiet mode.
), heating of the domestic hot water by
HP OFF
), heating of the domestic hot water
U
). See illustration.
). See illustration.
is
only
meaningfull
when
Quiet mode setting
Level 1
Level 2
Quiet
Quiet
Quiet
level 1
level 2
level 3
Normal
Quiet
Quiet
level 1
level 2
Quiet
Quiet
Quiet
level 1
level 2
level 3
Powerful
Powerful
Powerful
EKHVWQ002AAV3 + EKHHS200+260AA1V3
Domestic hot water heat pump
4PW65342-1A – 10.2010