Daikin F-Series Service Manual page 329

Hide thumbs Also See for F-Series:
Table of Contents

Advertisement

Outdoor Unit
Step
Remove the 2 sheets of
5
putty.
There is one nut fixing
6
the compressor.
Remove the nut with an
open-end spanner.
Before working, make
sure that the refrigerant is
empty in the circuit.
Be sure to apply nitrogen
replacement when
heating up the brazed
part.
Heat up the brazed part
7
of the discharge side
and disconnect (part
"a").
8
Heat up the brazed part
of the suction side and
disconnect (part "b").
9
Lift the compressor up
to remove.
318
Procedure
SiBE12-713
Points
Warning
Ventilate when refrigerant
leaks during the work.
(If refrigerant contacts fire, it
will cause to arise toxic gas.)
Removal Procedure