Omron CJ1W-PRT21 Operation Manual page 91

Profibus-dp slave unit
Hide thumbs Also See for CJ1W-PRT21:
Table of Contents

Advertisement

Error
Program-
ming
Console
display
Special I/O
SIOU
Unit Setup
SETUP
error
ERR
System
SYS FAIL
FAL error
FAL
72
Error
Flag and
code (in
word data
A400)
0500 to
A40202:
An installed Special I/O Unit
does not match the Special
055F
Special I/O
Unit Set-
I/O Unit registered in the I/O
ting Error
table.
Flag
The corresponding flag in
A428 to
A428 to A433 will be ON.
A433: Spe-
Bits A42800 to A43315 cor-
cial I/O Unit
respond to Machine num-
Setting
bers 0 to 95.
Error,
Machine
number
Flags
4101 to
A40215:
FAL(006) has been exe-
42FF
FAL Error
cuted in program.
Flag
Executed FAL Number
A360 to
Flags A36001 to A39115
A391: Exe-
correspond to FAL num-
cuted FAL
bers 001 to 511.
Number
The error code in A400 will
Flags
indicate the FAL number.
The leftmost digit of the
code will be 4 and the right-
most 3 digits of the code will
be from 100 to 2FF Hex and
will correspond to FAL num-
bers 001 to 511.
Probable cause
Change the registered I/O table.
Correct according to cause indicated by
FAL number (set by user).
Appendix
Possible remedy