Omron CJ1W-PRT21 Operation Manual page 62

Profibus-dp slave unit
Hide thumbs Also See for CJ1W-PRT21:
Table of Contents

Advertisement

Configuration information
15 14 13 12 11 10
D m+3
D m+3
Output start address (data from Master to Slave PLC)
Indicates the start address in the area indicated in D m+2, to
which the PROFIBUS output data, received from the master,
will be written. The value is provided by the PROFIBUS mas-
ter's Set_Prm telegram, and indicated in D m+3 after both the
Set_Prm and Chk_Cfg telegrams have been accepted.
The indication is only valid in case the output area code is une-
qual to 00.
The start address is indicated as a hexadecimal value in the
range 0000-7FFF (i.e. 0-32767 decimal).
15 14 13 12 11 10
D m+4
D m+4
Output data length(data from Master to Slave PLC)
The value indicates the size of the area to which the PROFI-
BUS output data, received from the master, will be written. The
value is provided by the PROFIBUS master's Chk_Cfg tele-
gram, and indicated in D m+4 after both the Set_Prm and
Chk_Cfg telegrams have been accepted.
The indication is only valid in case the output area code is une-
qual to 00.
The length (in words) is indicated as a hexadecimal value in
the range 0000-0064 (i.e. 0-100 decimal).
Note Before using the Slave output data in the PLC program, the user is to make
sure the Unit Status Flags (in CIO n+1) indicate that:
• PROFIBUS data exchange is active,
• there are no configuration errors,
and that the correct data format is selected. See section 4-6-3 Slave Output
Data . Otherwise the Slave Output words may contain invalid data.
9
8
7
6
5
4
3
9
8
7
6
5
4
3
Section 4-6
2
1
0
Output start address
2
1
0
Output data length
43