Control and status area
38
CIO n+1.12 Incorrect start address for slave input area
0: No error
1: There is an error in the slave input area mapping. The start
address of the area as specified in the Set_Prm telegram is
invalid for this PLC CPU type.
The BF LED is BLINKING to indicate a configuration- or
parameterisation error; no I/O data is transferred between
master and slave units.
CIO n+1.13 Incorrect end address for slave input area
0: No error
1: There is an error in the slave input area mapping. The end
address of the area as specified by the start address in the
Set_Prm telegram, plus the data length in the Chk_Cfg tel-
egram, is invalid for this PLC CPU type.
The BF LED is BLINKING to indicate a configuration- or
parameterisation error; no I/O data is transferred between
master and slave units.
CIO n+1.14 Incorrect start address for slave output area
0: No error
1: There is an error in the slave output area mapping. The
start address of the area as specified in the Set_Prm tele-
gram is invalid for this PLC CPU type.
The BF LED is BLINKING to indicate a configuration- or
parameterisation error; no I/O data is transferred between
master and slave units.
CIO n+1.15 Incorrect end address for slave output area
0: No error
1: There is an error in the slave output area mapping. The end
address of the area as specified by the start address in the
Set_Prm telegram, plus the data length in the Chk_Cfg tel-
egram, is invalid for this PLC CPU type.
The BF LED is BLINKING to indicate a configuration- or
parameterisation error; no I/O data is transferred between
master and slave units.
Section 4-5