Omron CJ1W-PRT21 Operation Manual page 90

Profibus-dp slave unit
Hide thumbs Also See for CJ1W-PRT21:
Table of Contents

Advertisement

Error
Program-
ming
Console
display
PC Setup
PC
error
SETUP
ERR
Battery
BATT
error
LOW
CPU Bus
CPU BU
Unit error
ERR
Special I/O
SIOU ERR 0300 to
Unit error
CPU Bus
CPU BU
Unit Setup
ST ERR
error
Error
Flag and
code (in
word data
A400)
009B
A40210:
There is a setting error in
PC Setup
the PC Setup. The location
Error Flag
of the error is written to
A406.
A406: PC
Setup Error
Location
00F7
A40204:
This error occurs when the
Battery
PC Setup has been set to
Error Flag
detect battery errors and the
CPU Unit's backup battery
is missing or its voltage has
dropped.
0200 to
A40207:
An error occurred in a data
020F
CPU Bus
exchange between the CPU
Unit Error
Unit and a CPU Bus Unit.
Flag
The corresponding flag in
A417: CPU
A417 is turned ON to indi-
Bus Unit
cate the problem Unit. Bits
Error,
A41700 to A41715 corre-
Machine
spond to Machine numbers
number
0 to F.
Flags
A40206:
An error occurred in a data
035F, or
Special I/O
exchange between the CPU
03FF
Unit Error
Unit and a Special I/O Unit.
Flag
The corresponding flag in
A418 to
A418 to A423 is turned ON
A423: Spe-
to indicate the problem Unit.
cial I/O Unit
Bits A41800 to A42315 cor-
Error,
respond to Machine num-
Machine
bers 0 to 95.
number
Flags
0400 to
A40203:
An installed CPU Bus Unit
040F
CPU Bus
does not match the CPU
Unit Set-
Bus Unit registered in the I/
ting Error
O table.
Flag
The corresponding flag in
A427: CPU
A427 will be ON. Bits 00 to
Bus Unit
15 correspond to Machine
Setting
numbers 0 to F.
Error,
Machine
number
Flags
Probable cause
Change the indicated setting to a valid
setting.
Check battery and replace if necessary.
Change the PC Setup setting if it is not
necessary to detect battery errors.
Check the Unit indicated in A417. Refer
to the Unit's operation manual to find
and correct the cause of the error.
Restart the Unit by toggling its Restart
Bit or turn the power OFF and ON again.
Replace the Unit if it will not restart.
Check the Unit indicated in A418 to
A423. Refer to the Unit's operation man-
ual to find and correct the cause of the
error. Restart the Unit by toggling its
Restart Bit or turn the power OFF and
ON again.
Replace the Unit if it will not restart.
Change the registered I/O table.
Appendix
Possible remedy
71