Omron CJ1W-PRT21 Operation Manual page 75

Profibus-dp slave unit
Hide thumbs Also See for CJ1W-PRT21:
Table of Contents

Advertisement

Protocol_Ident
Station_Type
Slave_Family
Revision
Hardware_Release
Software_Release
Bitmap_Device
Bitmap_Diag
Bitmap_SF
; Specific implementation information *****************************************/
Implementation_type = "SPC3"
Redundancy
Repeater_Ctrl_Sig
24V_Pins
Set_Slave_Add_supp
; Media access information ****************************************************/
Auto_Baud_supp
9.6_supp
19.2_supp
45.45_supp
93.75_supp
187.5_supp
500_supp
1.5M_supp
3M_supp
6M_supp
12M_supp
MaxTsdr_9.6
MaxTsdr_19.2
MaxTsdr_45.45
MaxTsdr_93.75
MaxTsdr_187.5
MaxTsdr_500
MaxTsdr_1.5M
MaxTsdr_3M
MaxTsdr_6M
MaxTsdr_12M
Min_Slave_Intervall = 5
56
= 0
= 0
= 10
= "V2.2"
= "V1.1"
= "V2.0"
= "OC0602_R"
= "OC0602_D"
= "OC0602_S"
= 0
= 2
= 0
= 0
= 1
= 1
= 1
= 1
= 1
= 1
= 1
= 1
= 1
= 1
= 1
= 60
= 60
= 60
= 60
= 60
= 100
= 150
= 250
= 450
= 800
; Profibus-DP supported.
; Station = DP-Slave.
; Slave family = 10 (PLC).
;
; Device revision 2.2.
; Hardware revision 1.1.
; (0991860-9A).
; Software revision 2.0.
;
; Bitmap RUNNING
; Bitmap DIAGNOSTIC
; Bitmap SPECIAL
;
;
; DP protocol.
; handled by SPC3.
; Redundancy NOT supported.
; Supported, TTL level
; No external 24 Volt input.
;
; Station address is set
; through hardware address
; selectors.
; Automatic baud rate select
; (SPC3 specific feature).
; Supported baud rates:
; 9600 Baud
; 19.2 kBaud
; 45.45 kBaud
; 93.75 kBaud
; 187.5 kBaud
; 500 kBaud
; 1.5 MBaud
; 3 MBaud
; 6 MBaud
; 12 MBaud
; Max. response times:
; 60 Tbit = 6.25 msec.
; 60 Tbit = 3.125 msec.
; 60 Tbit = 1.32 msec.
; 60 Tbit = 640 usec.
; 60 Tbit = 320 usec.
; 100 Tbit = 200 usec.
; 150 Tbit = 100 usec.
; 250 Tbit = 83 usec.
; 450 Tbit = 75 usec.
; 800 Tbit = 67 usec.
;
; Minimum slave interval =