Communications Parameters; Communications Parameter Setup - Omron E5CN-HT Communications Manual

Digital
Hide thumbs Also See for E5CN-HT:
Table of Contents

Advertisement

SECTION 1 Communications Methods

■ Communications Parameters

Item
Communications protocol
Communications unit number
Communications baud rate
Communications data length
(See note.)
Communications stop bits
Communications parity
Send data wait time
● Communications Parameter Setup
1-8
The E5CN/AN/EN-HT's communications specifications are set in the commu-
nications setting level. These parameters are set on the E5CN/AN/EN-HT's
front panel. The following table shows the communications parameters and
their setting ranges.
Code
psel
CompoWay/F or Modbus
u-no
0 to 99
bps
1.2/2.4/4.8/9.6/19.2/38.4/57.6
(kbit/s)
len
7/8 (bit)
sbit
1/2
prty
None, Even, Odd
sdwt
0 to 99
Note: The communications data length for Modbus must be 8 bits.
Before you carry out communications with the E5CN/AN/EN-HT, set up the
communications unit number, baud rate, and other parameters by carrying out
the following procedure. For details on operations other than communications
parameter setup, refer to E5CN/AN/EN-HT Digital Controllers Program Type
User's Manual (Cat. No. H169) for the devices being used.
1.
Press the O Key for at least three seconds to move from the "operation
level" to the "initial setting level."
2.
Press the O Key for less than one second to move from the "initial setting
level" to the "communications setting level."
3.
Select the parameters as shown below by pressing the M Key.
Settings
cwf/mod
0,1
to 99
1.2/2.4/4.8/9.6
(kbit/s)
7
/8 (bit)
1/
2
none/
0 to 99 ms, default time:
Highlighted values indicate default settings.
Set Values