High Pressure Control In Cooling - Daikin CTXG09QVJUW Service Manual

Multi-split type air conditioners 2/3/4mxs-n series
Hide thumbs Also See for CTXG09QVJUW:
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit

7.13 High Pressure Control in Cooling

F6
Error Code
Outdoor Unit LED
A
Display
Method of Error
High pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Detection
Error Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.191
Check No.12
Refer to P.194
Check No.17
Refer to P.198
Check No.18
Refer to P.198
Check No.19
Refer to P.199
178
j
i
h
i
i
1
2
3
4
The temperature sensed by the outdoor heat exchanger thermistor rises above about
(149°F).
The error is cleared when the temperature drops below about
The installation space not large enough
Dirty outdoor heat exchanger
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the installation space.
Check No. 17
Check the installation
condition.
OK
Check No. 19
Check the outdoor fan.
OK
Check No. 18
Check the discharge
pressure.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 01
Check the outdoor heat
exchanger thermistor.
OK
h
5
NG
NG
NG
NG
NG
SiUS121630EA
65
°C (121.1°F).
49.5
Change the installation
location or direction.
Clean the outdoor heat
exchanger.
Replace the outdoor fan
motor.
Reconnect the connector or
fan motor lead wires.
Replace the stop valve.
Replace the electronic
expansion valve or the coil.
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
(R20418)
Service Diagnosis
°C

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents