SiUS121630EA
5.7

Mismatching of Indoor Unit and Outdoor Unit

UA
Error Code
Method of Error
The supply power is detected for its requirements (pair type is different from multi type) by the
indoor/outdoor transmission signal.
Detection
Error Decision
The pair type and multi type are interconnected.
Conditions
Supposed
Causes
Troubleshooting
Service Diagnosis
Wrong models interconnected
Wrong wiring of connecting wires
Wrong indoor unit PCB or outdoor unit PCB mounted
Defective indoor unit PCB
Defective outdoor unit PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the
combination of the
indoor
and outdoor unit.
OK?
YES
Are the
connecting wires connected
properly?
YES
Troubleshooting for CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series
NO
NO
Match the compatible models.
Correct the connection.
Check the part numbers of the
indoor and outdoor unit PCB
with the Parts List.
If not matched, change for the
correct PCB.
(R23001)
147