Error codes
SIRIUS 3RW44 manual
GWA 4NEB 535 2195-02 DS 06
The following error codes are generated by the soft starter:
Error codes
byte
High
Low
00 H
00 H
No error
Communication interface
80 H
A0 H Negative acknowledgement
"Read data set"
80 H
A1 H Negative acknowledgement
"Write data set"
80 H
A2 H Protocol error
80 H
A9 H This function is not supported!
Technology access
80 H
B0 H Unknown data set number
80 H
B1 H Incorrect data set length when writing
80 H
B2 H Incorrect slot number
80 H
B6 H Communication partner declined data
acceptance!
80 H
B8 H Invalid parameter
Device resources
80 H
C2 H Temporary lack of resources in the
device!
Table 8-15: Error codes
PROFIBUS DP Communication Module
Error message
Cause
• Data set can only be written
• Data set can only be read
• Layer 2 (field bus)
• Device interface
• Incorrect coordination
• DPV1 service does not
support reading/writing of the
data set
• Data set number not known in
the soft starter
• Data set length differs from
data set length specified
• Slot number not 1 or 4
• Incorrect operating mode
(automatic, manual bus,
manual operation local)
• Data set can only be read
• Parameter changes not
permissible when ON
• Incorrect parameter value
• No available receive buffer
• The data set is currently being
updated
• The data set order is currently
active at another interface