Siemens Milltronics BW100 Instruction Manual page 8

Integrator for belt scales
Table of Contents

Advertisement

Inputs
• load cell:
• speed sensor:
• auto zero:
Outputs
• analog:
• resolution:
• load cell:
• speed sensor:
• remote totalizer 1:
• remote totalizer 2:
• relay output:
Communications
• Dolphin compatible
• proprietary bipolar current loop
Cable/Separation:
• one load cell/LVDT:
non-sensing:
sensing:
• two load cells:
non-sensing:
sensing:
• speed sensor
• auto zero:
• remote total:
Page 4
0 - 45 mV dc per load cell
pulse train: 0-5 V low, 5-15 V high, 1 to 2000 Hz,
open collector switch
relay dry contact
dry contact from external device
- optically isolated 0/4 - 20 mA
- 750
- 0.1% of 20 mA
- 10 Vdc compensated for strain gauge type, 2 cells max
- 12 Vdc, 50 mA max excitation
- contact closure 32 - 288 ms duration
- open collector switch rated 30 Vdc, 100 mA max
- contact closure 32 - 288 ms duration
- open collector switch rated 240 Vac/dc, 100 mA max
programmable function 1 form C SPDT relay contact rated
5 A at 250 Vac, non-inductive
Belden 8404, 4 wire shielded, 20 AWG or equivalent,
150 m (500 ft.) max.
Belden 9260, 6 wire shielded, 20 AWG or equivalent,
300 m (1000 ft.) max.
Belden 9260, 6 wire shielded, 20 AWG or equivalent,
150 m (500 ft.) max.
Belden 8418, 8 wire shielded, 20 AWG or equivalent,
300 m (1000 ft.) max.
Belden 8770, 3 wire shielded, 18 AWG or equivalent,
300 m (1000 ft.) max.
Belden 8760, 1 pair, twisted/shielded, 18 AWG, 300 m
(1000 ft.) max.
Belden 8760, 1 pair, twisted/shielded, 18 AWG, 300 m
(1000 ft.) max.
Milltronics BW100 - INSTRUCTION MANUAL
or
or
max loading
7ML19985DJ01