P200 mA Range
Sets the range for the mA output.
Entry:
1 = 0 - 20 mA
2 = 4 - 20 mA
P201 mA Function
Assigns the mA output to track one of the integrator functions.
Entry:
1 = rate
2 = load
3 = speed
P212 mA Min Limit
Limits the lower mA range (0 or 4 mA) to a minimum output value.
Enter limit value, range 0 - 22.
P213 mA Max Limit
Limits the upper mA range (20 mA) to a maximum output value.
Enter limit value, range 0 - 22.
P214 4 mA Trim
Adjusts the 4 mA output level to agree with a milliammeter or other external mA input
device.
Enter trim value, range 0 - 9999.
P215 20 mA Trim
Adjusts the 20 mA output level to agree with a milliammeter or other external mA input
device.
Enter trim value, range 0 - 9999
P220 mA Output Damping
Sets the speed at which the mA output reacts to change.
The greater the damping value, the slower the response. If the value is 0, the mA output
assumes the damping set in P080.
Enter the damping value, range 0 - 9999
End of mA output parameters.