3 SPECIFICATIONS
Device No.
Signal name
Y1
Y3
CH.
Offset
Y5
Setting Request
Y7
Y2
Y4
CH.
Gain
Y6
Setting Request
Y8
Operation
Y9
Condition Setting
Request
User Range Write
YA
Request
Error Clear
YF
Request
3 - 8
(2) Output signals
(1) This signal is made valid in the offset/gain setting mode.
(2) This signal corrects the temperature conversion value to be an offset temperature
set value when it is on.
(3) When this signal turns on while the Gain Setting Request on the same channel is on
or they turn on simultaneously, an error will occur and the operation in (2) not
performed.
(4) For the on/off timing, refer to the field of the CH.
(X1 to 4).
(1) This signal is made valid in the offset/gain setting mode.
(2) This signal corrects the temperature conversion value to be a gain temperature set
value when it is on.
(3) When this signal turns on while the Offset Setting Request on the same channel is
on or they turn on simultaneously, an error will occur and the operation in (2) not
performed.
(4) For the on/off timing, refer to the field of the CH.
(X1 to 4).
(1) This signal is turned on when the "conversion enable/disable designation", "CH.
averaging time/count", "averaging processing designation", "CH.
enable/disable designation", "CH.
"CH.
warning output upper/lower limit value" is made valid.
(2) When this signal turns on, the Disconnection Detection Flag (XC) and Warning
Output Signal (XD) turn off.
(3) For the on/off timing, refer to the field of the Operation Condition Setting Completed
Signal (X9).
(1) This signal is turned on/off when the value whose offset/gain setting adjustment is
completed is registered.
(2) For the on/off timing, refer to the field of the User Range Write Status Signal (XA).
(1) This signal is turned on when the Error Occurred Signal (XF) and Disconnection
Detection Flag (XC) are cleared.
However, the set value error of the intelligent function module switch setting cannot
be cleared. Correct the set value.
(2) For the on/off timing, refer to the field of the Error Occurred Signal (XF).
Description
Offset/Gain Setting Status Signal
Offset/Gain Setting Status Signal
scaling range upper/lower limit value" or
MELSEC-Q
warning output
3 - 8