Siemens SIMATIC ET 200SP Manual page 44

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Modes and Functions
3.4 Pulse train mode
Feedback interface:
Offset to the start address
Channel 0
Channel 1
1
Byte 0: Bit 0
Byte 8: Bit 0
Byte 0: Bit 1
Byte 8: Bit 1
Byte 0: Bit 2
Byte 8: Bit 2
Byte 0: Bit 3
Byte 8: Bit 3
Byte 0: Bit 4
Byte 8: Bit 4
Byte 0: Bit 5
Byte 8: Bit 5
Byte 0: Bit 7
Byte 8: Bit 7
Byte 1: Bit 2
Byte 9: Bit 2
Byte 1: Bit 4
Byte 9: Bit 4
Byte 1: Bit 5
Byte 9: Bit 5
Byte 2: Bit 0
Byte 8: Bit 0
Byte 2: Bit 1
Byte 10: Bit 1
44
Parameter
Meaning
ERR_PWR
Bit 0
0
1
ERR_24V
Bit 1
0
1
ERR_LD
Bit 2
0
1
ERR_PULSE
Bit 3
0
1
ERR_DQA
Bit 4
0
1
ERR_DQB
Bit 5
0
1
ERR_SLOT_VAL
Bit 7
0
1
STS_LD_SLOT
Bit 2
STS_READY
Bit 4
0
1
STS_SW_ENABLE
Bit 5
0
1
STS_ENABLE
Bit 0
0
1
STS_DQA
Bit 1
0
1
Indicates under voltage on the Power supply. Note that the bit is not set
if the voltage is not present.
PWR is not under voltage
PWR is detected, but under voltage
Indicates a short-circuit or overload on the output 24 V DC.
You must set the RES_ERROR (control interface) to reset this error.
No short-circuit on 24 V DC
Short-circuit on 24 V DC
Indicates an error while loading a value using the field SLOT (only in
"single-update" SLOT-mode).
No load error pending
Load error pending: you must set the RES_ERROR (control interface)
to reset this error and be able to use the SLOT again.
Indicates a pulse output error.
No pulse output error
Pulse output error
Indicates a short-circuit on the output DQn.A. You must set
RES_ERROR (control interface) to reset this error.
No short-circuit on DQn.A
Short-circuit on DQn.A
Indicates a short-circuit on the output DQn.B or an attempt to set both
DQs manually using SET_DQA, SET_DQB, and TM_CTRL_DQ. You
must set RES_ERROR (control interface) to reset this error.
No short-circuit on DQn.B
Short-circuit on DQn.B, or attempt to set both DQn.A and DQn.B
Indicates that an invalid value is detected in SLOT
(only in "permanent-update" SLOT-mode).
SLOT value is valid
SLOT value is not valid
Toggle acknowledge bit for each action of the SLOT in "single-update"
SLOT-mode.
Each toggle of this bit means a successful LD_SLOT action.
Indicates the module is ready and parameterized.
Module is not parameterized
Module is parameterized
Indicates the status of SW_ENABLE (control interface).
SW_ENABLE cleared
SW_ENABLE set
Indicates an output sequence is running.
Output sequence not running
Output sequence running
Indicates the signal level at the DQn.A digital output.
0 at the DQn.A digital output
1 at the DQn.A digital output