Parameter data record
Bit →
7
Byte
7
Reserved
Must be set to 0.
1
Table A- 2
Channel 0 Word, DWord, and Real values configuration
Byte
Channel 0 mode and variable usage
8 to 11
PWM (only if current-control is inactive)
Pulse output, Pulse train, On/Off-delay, and Frequency output Reserved
12 to 15
PWM, Pulse train
DC motor
Pulse output, On/Off-delay, and Frequency output
16 to19
Pulse output, PWM, Pulse Train, Frequency output, and DC
motor
On/Off-delay
20 to 23
PWM
Pulse train
On/Off-delay
Pulse output, Frequency output, and DC motor
140
6
5
Output format
1
Bits
PWM or
5
Pulse
and
train
4
00
S7 Ana-
B
log format
01
Per 100
B
(%)
10
Per 1,000
B
11
Per
B
10,000
Minimum pulse duration DWord
4
3
Diagnos-
tics DQB
Fre-
DC
0
: Disa-
B
quency
motor
ble
output
1
: Ena-
B
ble
Re-
S7
served
Analog
format
1 Hz
Re-
served
Re-
Re-
served
served
Re-
Re-
served
served
Value range
Minimum pulse duration:
Default value = 0 μs
Period duration DWord
Period duration:
High-speed disabled: 100 μs to 85,000,000 μs
High-speed enabled: 10 μs to 85,000,000 μs
Default value = 2,000,000 μs
Period duration:
100 μs to 85,000,000 μs
Default value = 1000 μs
Reserved
On-delay DWord
On-delay: 0 μs to 85,000,000 μs
Reserved
Value DWord
Dithering ramp times (2 bytes each):
Ramp-up time (low word): 0 ms to 30,000 ms
Ramp-down time (high word): 0 ms to 30,000 ms
Duty cycle %: 0 to 27648, Default = 50 (50%)
Off-delay: 0 μs to 85,000,000 μs
Reserved
Technology module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
2
1
Diagnostics
Substitute
DQA
value DQB
0
: Disable
0
: 0 V
B
B
1
: Enable
1
: 24V
B
B
Manual, 09/2015, A5E35061186-AA
0
Substitute
value DQA
0
: 0 V
B
1
: 24V
B