Parameter Validation Errors - Siemens SIMATIC ET 200SP Manual

Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Interrupts/diagnostic messages

7.2 Parameter validation errors

7.2
Parameter validation errors
If the TM Pulse 2x24V parameter record is modified with an incorrect parameter value, then
the module returns the error codes shown in the following table.
During TIA Portal Device configuration, parameter values are verified before transfer to the
module. This prevents parameter errors during the static TIA Portal Device configuration.
You can modify the parameter data record during runtime with the WRREC (Write Record)
program instruction.
For example, an illegal mode value is written to the module by WRREC execution. After
execution the WRREC STATUS output is an ARRAY[1..4] of BYTE data with the value
16#DF80E111.
Example WRREC
STATUS data
DF
H
80
H
E1
H
11
H
Error code
Parameter
11
Mode
H
12
Reaction to CPU STOP
H
1A
Input delay
H
1B
Period duration
H
1C
On-delay
H
1D
Minimum pulse duration
H
1E
Off-delay
H
20
Reference value current
H
21
Period duration
H
22
Dithering
H
23
High-speed output
H
24
Current control
H
25
Current control and high-speed
H
output
120
Address
STATUS[1]
STATUS[2]
STATUS[3]
STATUS[4]
Validation criteria
Reserved value
Reserved value
Reserved value
Greater than maximum
Greater than maximum
Greater than maximum
Greater than maximum
Greater than maximum
Lower than minimum
Not disabled
Not disabled
Not disabled
Both enabled
Meaning
Write data record error
Error according to IEC 61158-6
Module specific error
Module error code from row 1 in the following table:
Mode parameter has an incorrect reserved value.
Mode
All modes
All modes
All modes
PWM
Pulse train
DC motor
Pulse output
PWM
Frequency output
DC motor
PWM
On/Off-delay
PWM
PWM
Pulse train
DC motor
Pulse output
Pulse train
On/Off-delay
Frequency output
DC motor
DC motor
All modes with parallel connection
Pulse output
Pulse train
On/Off-delay
Frequency output
DC motor
PWM
Technology module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)