5 Remote I/O Slave Communications
5-1-3

Procedures for Using Remote I/O Slave Communications

Fixed Allocations for Remote I/O
Switch the CPU Unit to PROGRAM mode.
Change "*_Sw2SlavDsblCmd" (Slave Stop Switch) to TRUE from the Sysmac Studio.
Change "*_Sw2SlavFixAloc1Cmd" to "*_Sw2SlavFixAloc3Cmd"
(Slave Fixed Allocation Setting 1 to 3 Switch) to TRUE from the Sysmac Studio.
Change "*_Sw2SlavEnblCmd" (Slave Enable Switch) to TRUE from the Sysmac Studio.
Define user-defined variables in the area to which I/O data is allocated.
Switch the CPU Unit to RUN mode.
Slave remote I/O communications will begin.
Note Slave communications must be disabled prior to area allocation and must be enabled
after area allocation. The order of the procedure is 1) stop slave communications, allo-
cate areas, and then enable slave communications. The allocated areas will not be valid
if the procedure is done in any other order.
5-4
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)