Start-up and settings
Enable configuration:
g Code 3, display: No
Turn
, Code 3 blinks.
Press
Turn
YES
Press
, display:
Perform zero calibration:
Turn
Code 6
Press
, Code 6 blinks.
Turn
ZP
Î Press INIT key!
Zero calibration starts. The positioner
moves the valve to the CLOSED position
and recalibrates the internal electrical
zero point.
7.8 Reset to default settings
A reset allows the positioner to be reset to
the default settings. To reset the positioner,
the options DIAG, STD and DS are available
in Code 36. Table 9 lists the reset functions.
Note:
Code 36 – DS is usually selected
when the valve is mounted in another
position or when the positioner is to
be mounted to another valve.
Performing a reset does not necessar-
ily mean the positioner must be
re-initialized.
82
Init mode
Default MAX
Enable configuration:
g Code 3, display: No
Turn
, Code 3 blinks.
Press
Turn
YES
Press
, display:
Reset start-up parameters:
Turn
g Code 36, display: – – –
Press
, Code 36 blinks.
Turn
DIAG/STD/DS
Press
.
The parameters are reset depending on the
option selected. See following Table 9.
Reset
Default: No
EB 8384-6 EN