g Code 3, display: No
Turn
Press
, Code 3 blinks.
Turn
YES
Press
, display:
Enter the pin position and nominal range:
mm
mm
Turn
Code 4
, Code 4 blinks.
Press
Turn
Pin position on lever (see relevant
section on attachment)
Press
.
Turn
Code 5
, Code 5 blinks.
Press
Turn
Nominal travel of the valve
Press
.
EB 8384-6 EN
Enable configuration
Default: No
Pin position
Default: No
Nominal range
(locked when Code 4 = No)
Select the initialization mode:
Turn
Code 6
Press
.
SUB
Turn
Press
to confirm the SUB as the initializa-
tion mode.
Enter the direction of action:
Turn
Code 7
, Code 7 blinks.
Press
Turn
Direction of action (ää/äæ)
Press
.
Deactivate travel limit:
Turn
Code 11
Press
, Code 11 blinks.
Turn
g No
Press
.
Start-up and settings
Init mode
Default MAX
Direction of action
Default
Travel limit
Default: No
79