Samson Series 3730 Mounting And Operating Instructions page 103

Type 3730-6 electropneumatic positioner
Table of Contents

Advertisement

Code
Parameter – Readings/
no.
values [default setting]
36* Reset
(continued)
37 Options
Read only
38* Inductive limit contact
[No], YES, ESC
39 Set point deviation e info
Read only
40 Min. transit time OPEN
Read only
41 Min. transit time CLOSED
Read only
42 Set point
Read only
43 Firmware version
Read only
EB 8384-6 EN
Description
DAG:
Reset diagnostics assessment
− Parameter settings, reference values and logs remain
unchanged.
− The positioner does not need to be re-initialized.
DS:
Resets positioner to default settings.
− Resets parameters to their default settings.
− Resets diagnostics assessment.
− Information parameters (read only) are deleted.
− Re-initialize positioner.
Indicates which option (terminals 31 and 32, Fig. 20) is installed.
No: No option installed
POS: Analog position transmitter
dI: Binary input
LS: Leakage sensor
XI: 4 to 20 mA x input
When the binary input is used, DI and HIGH or LOW status are
displayed in alternating sequence.
When the leakage sensor is used, LS and the detected sound level
in dB are displayed in alternating sequence.
Indicates whether the inductive limit contact option is installed or
not.
Difference of the target position (e = w – x)
Minimum opening time determined during initialization
Minimum closing time determined during initialization
Set point w used in automatic mode
4 to 20 mA correspond to 0 to 100 %
Device type and current firmware version (displayed in alternating
sequence)
Code list
103